Using Fins Applications; Cx-Programmer (Cx-Server) - Omron CJ1W-EIP21 - 10-2010 Operation Manual

Ethernet/ip units
Table of Contents

Advertisement

Using FINS Applications

8-5

Using FINS Applications

8-5-1

CX-Programmer (CX-Server)

CX-Programmer/CX-Integrator
Node number: 1
IP address: 192.168.250.1
Ethernet port
Ethernet or EtherNet/IP (Network address: None)
The following examples show how to connect online from a CX-Programmer
on an Ethernet network to a PLC on the Ethernet network.
System Configuration Example 1: No Routing
In this example, an online connection is made by FINS/UDP to a PLC on an
Ethernet network (PLC1 in the diagram below) from a CX-Programmer/CX-
Integrator connected to the Ethernet network.
Conditions
• FINS/UDP method
• IP Address Conversion: Automatic (Dynamic) generation method
FINS/UDP method
CX-Programmer's Change PLC Dialog Box
Settings for target PLC (PLC1)'s Change PLC Dialog Box
PLC name
Network classification
Network Tab Page
Driver Tab Page
CX-Programmer's FINS/UDP Tab Page in Edit Parameters Dialog Box
Item
FINS/UDP Port
IP Address Conversion
IP Router Table
EtherNet/IP Unit
IP address conversion: Automatic
generation method (dynamic)
EtherNet/IP Unit node number: 2
EtherNet/IP Unit IP address: 192.168.250.2
Target: PLC1
FINS transmission source address
FINS destination
Network number 0
Node address
Frame length
Response monitor time
Workstation node address
Automatic generation method
IP address
Port number
Default (9600)
Automatic (Dynamic) generation method
None
Section 8-5
Setting
PLC1
Ethernet
0
2
2,000 bytes
2 seconds
1
Not selected
192.168.250.2 (Eth-
erNet/IP Unit or
built-in EtherNet/IP
port IP address)
9600
Setting
211