Node number: 1
IP address: 192.168.250.1
Ethernet port
Ethernet (Network address: None)
128
The following examples show how to connect online from a CX-Programmer
on an Ethernet network to a PLC on the Ethernet network.
System Configuration Example 1: No Routing
In this example, an online connection is made by FINS/UDP to a PLC on an
Ethernet network (PLC1 in the diagram below) from a CX-Programmer or CX-
Integrator connected to the Ethernet network.
Conditions
• FINS/UDP method
• IP address conversion: Automatic generation method (dynamic)
FINS/UDP method
CX-Programmer's Change PLC Dialog Box
Settings for target PLC (PLC1)'s Change PLC Dialog Box
PLC name
Network classification
Network Tab
Driver Tab
Ethernet Unit
IP address conversion: Automatic
generation method (dynamic)
Ethernet Unit node number: 2
Ethernet Unit IP address: 192.168.250.2
Target: PLC1
FINS transmission source address
FINS destination
Network number 0
Node address
Frame length
Response monitor time
Workstation node address
Automatic generation method
IP address
Port number
Section 6-5
Setting
PLC1
Ethernet
0
2
2,000 bytes
2 seconds
1
Not selected
192.168.250.2
(Ethernet Unit IP
address)
9600