Troubleshooting

Error
code
(hex)
03D3
Link OFF error
03D4
Verification error (Tag data link only)
Note For details on identifying the cause of
the verification error, refer to 14-3
Connection Status Codes and Error
Processing.
This error will not be stored when a
target node is missing for version 2.0
or higher.
03D5
Tag data link error
0601
CPU Bus Unit error
0602
CPU Bus Unit memory error
Note

14-5 Troubleshooting

14-5-1 CPU Unit's ERR/ALM Indicator Lit or Flashing

368
Error
00 hex
Connection instance num-
ber (0 to 255)
00 hex
Variable
01: Read error
02: Write error
If a memory error occurs in the error log area of EEPROM, the record will not
be stored in EEPROM.
Use the following table to troubleshoot the system when the CPU Unit's ERR/
ALM indicator is lit or flashing when the EtherNet/IP Unit or built-in EtherNet/
IP port is mounted.
An I/O verification
error occurred.
A CPU Bus Unit
setting error
occurred.
A CPU Bus error
occurred.
An I/O Bus error
occurred.
For details, refer to the CPU Unit's Operation Manual.
Detail code
First byte
00 hex
Lower byte of IP address
Lower byte of IP address
02 hex: Network parame-
ter
06 hex: Error log
09 hex: Identity data
0E hex: Unit name
0F hex: Ethernet basic
setting
10 hex: Ethernet
advanced setting
11 hex: MAC address
12 hex: Status area layout
setting
14 hex: Term Tag address
resolution memory write
error
• Confirm that the Unit is connected properly.
• Check the I/O table with the I/O Table Verification operation
and correct it if necessary. After correcting it, perform the I/O
Table Create operation.
• The CPU Bus Unit model registered in the I/O tables does
not match the model of CPU Bus Unit actually mounted.
Check the I/O tables with the I/O Table Verification operation
and correct it if necessary.
After correcting the I/O tables, perform the I/O Table Create
operation.
• Confirm that the Unit is connected properly.
• Restart the Unit. Replace the Unit if it doesn't restart.
• Confirm that the Unit is connected properly.
• Restart the Unit. Replace the Unit if it doesn't restart.
Section 14-5
Saved in
EEPROM
Second byte
No
No
No
Yes
Yes
(See
note.)