Automatic Clock Adjustment

12-1 Automatic Clock Adjustment

12-1-1 Overview

Note
324
The EtherNet/IP Unit or built-in EtherNet/IP port can obtain the clock informa-
tion from the SNTP server (see note 1) at a particular time or when a desig-
nated bit turns ON and then refresh the internal clock information of the CPU
Unit to which it is mounted (referred to as the local CPU Unit).
Intranet
SNTP server
Automatic clock adjustment
Ethernet
24: 00: 00
Clock data is obtained from the
SNTP server and written at a particular
time or when a designated bit turns ON.
(1) The SNTP (Simple Network Time Protocol) server is used to control the
time on the LAN.
(2) An error will occur in the following CPU Units when the automatic clock
adjustment function is executed under the conditions shown in the table.
CPU Unit
CPU Units manufactured on or
before January 31, 2003 (lot num-
bers 030131 or earlier):
@@
CJ1G-CPU
H
@@
CJ1H-CPU
H
@@
CS1G-CPU
H
@@
CS1H-CPU
H
(3) The manufacturing date can be determined from the lot number on the
side or top corner of the CPU Unit.
(4) The lot numbers are as follows:
YYMMDDnnnn, in which YY indicates the last two digits of the year, MM
the month, DD the day, and nnnn the serial number.
(5) In accordance with SNTP protocol specifications, automatic adjustment
will not be possible from February 7, 2036. In EtherNet/IP Units or built-
in EtherNet/IP ports, this function will no longer operate from February 7,
2036 (an error message will not be displayed).
The clock information can be broadcast to other CPU Units on the same Network.
24: 00: 00
EtherNet/IP Unit or
built-in EtherNet/IP port
Conditions
When the CPU execution mode is set to other
than normal mode (priority peripheral servicing
mode, parallel processing with synchronous
memory access mode, or parallel processing
with asynchronous memory access mode).
AND
When the CPU Unit operating mode is set to
RUN or MONITOR mode.
Section 12-1

Advertisement

Table of Contents
loading

Table of Contents