Closed-Loop Control Settings (P052 = 5) - Siemens SIMOVERT MASTERDRIVES 6SE7087-6CX86-2BA1 Manual

Active front end (afe) afe rectifier / regenerative feedback unit ac-dc modular design for construction types e to j
Table of Contents

Advertisement

Parameterization
P052 = 5
P052 = 0
P
11.2.6

Closed-loop control settings (P052 = 5)

Function
Condition
Result
P052 = 5
P051 = 3
P052 = 0
P
11-10
Select "Closed-loop control settings"
(see Section "Closed-loop control settings")
Select "Return"
The operating display (r000) appears. At the same time,
parameters and internal quantities are set to new values
depending on the function selection.
The hardware is initialized.
If one of the fault messages F050/F070/F080 appears, see Section
"Fault and alarm messages".
On completion of the selected function, operating display STARTING
LOCKOUT (008) or READY FOR ON (009) appears.
This function is used to alter the closed-loop control settings (AFE
data).
The "Closed-loop control settings" can be made in the FAULT (007),
STARTING LOCKOUT (008) or READY FOR ON (009).
All parameters which can be written in the "Closed-loop control
settings" state ("A", see right-hand column in Parameter List) can be
altered by this function.
"Closed-loop control settings" is terminated by resetting the status
(P052 = 0) with calculation of internal quantities.
Select "Closed-loop control settings"
Access level "Expert Mode"
(in case parameters which require Export Mode need to be
altered)
Change selected parameters which can be altered in the "Closed-loop
control settings" state.
Select "Return"
The operating display (r000) appears. At the same time,
parameters and internal quantities are set to new values
depending on the function selection.
On completion of the selected function, operating display STARTING
LOCKOUT (008) or READY FOR ON (009) appears.
6SE7087-6CX86-2BA1
Operating Instructions SIMOVERT MASTERDRIVES AFE
06.2005
Siemens AG