Servo On And Emergency Stop - Yamaha CC-Link RCX Series Owner's Manual

Robot controller
Table of Contents

Advertisement

c
CAUTION
• The dedicated input ON/OFF
process from the master station
PLC to the controller must be
carried out at an interval of
100ms or more. If the interval is
too short, the dedicated input may
not be recognized. (This also
applies to the same dedicated
input and differing dedicated
input intervals.)
• If dedicated outputs are provided
for the dedicated inputs from the
master station PLC to controller,
use them.
3.2

Servo ON and emergency stop

on
RXn0:SO ( 00 )
Emergency stop input
off
status output
on
RXn1:SO ( 01 )
CPU_OK output
off
on
RXn2:SO ( 02 )
Servo ON status output
off
on
RXn3:SO ( 03 )
Alarm status output
off
on
RYn0:SI ( 00 )
Emergency stop input
off
on
RYn1:SI ( 01 )
Servo ON input
off
Initial servo ON process after power ON
a) Servo ON input ON is input
b) If not in the emergency stop state, output servo ON status ON is output
c) After confirming that servo ON status output is ON, servo ON input OFF is input
Shift to emergency stop
d) Emergency stop input OFF is input
e) Emergency stop input status and alarm status output ON are output
Servo ON status output OFF is output
Servo ON process from emergency stop status
f) Emergency stop input ON is input
g) Emergency stop input status output OFF is output
h) Servo ON input ON is input
i) Alarm status output OFF is output
j) Servo ON status output ON is output
k) After confirming that servo ON status output is ON, servo ON input OFF is input
* The servo is OFF when the controller power is turned ON.
* When SAFE mode is enabled, dedicated inputs other than SI (00) and SI (11) might be
disabled depending on service mode parameter setting unless service mode input sig-
nal is set to ON with SI (02) in the CC-Link system.
Get other manuals https://www.bkmanuals.com