Warning And Alarm Displays; Warning And Alarm Definitions - Trane Thermafit AMC Series Installation, Operation And Maintenance Manual

Modular air-cooled chiller
Table of Contents

Advertisement

Warning and Alarm Displays

Warning
Alarm
Trip-Lock

Warning and Alarm Definitions

The warning/alarm information below defines each
warning/alarm condition, provides the probable cause for
the condition, and details a remedy or troubleshooting
procedure.
ARTC-SVX008A-EN
An alarm or trip-lock alarm will flash on display along with
the alarm number. In addition to the text and alarm code on
the frequency converter LCP, there are three status
indicator lights.
Warning LED
On
Off
On
Hazardous Service Procedures!
Failure to follow all precautions in this manual and on
the tags, stickers, and labels could result in death or
serious injury.
Technicians, in order to protect themselves from
potential electrical, mechanical, and chemical
hazards, MUST follow precautions in this manual and
on the tags, stickers, and labels, as well as the
following instructions: Unless specified otherwise,
disconnect all electrical power including remote
disconnect and discharge all energy storing devices
such as capacitors before servicing. Follow proper
lockout/tagout procedures to ensure the power can
not be inadvertently energized. When necessary to
work with live electrical components, have a qualified
licensed electrician or other individual who has been
trained in handling live electrical components perform
these tasks.
Optional Variable Frequency Drive
Alarm LED
Off
On (Flashing)
On (Flashing)
WARNING
A–3