Operating Procedures
Figure 20. Alarm history
Sorting
Alarm history list can be sorted by any column in ascending
or descending order by tapping the corresponding column
heading. The triangle that appears next to the heading
indicates which column is being sorted and the direction of
sorting.
Sorting is applied to the alarm time column in ascending
order by default, which is indicated when the triangle is
pointing up. Ascending order for the alarm time column
requires that earlier records appear on the list first. For all
other columns, alphabetical sorting applies.
History Alarms CSV Export generates history alarms log as
CSV file that can be stored.
Duration
Allows selecting the time period for which the alarm history
is displayed. Once the selection is made from the drop-
down menu, pressing the REFRESH button updates the list
and then From and To timestamps get updated
accordingly.
Time
This is the time stamp that is displayed when the alarm
state was changed.
Name
This column gives alarm name.
Status
This column displays the alarm state. There are five
possible states for any alarm:
Triggered Not Acked – Alarm triggered (active) but not
acknowledged
Triggered Acked – Alarm triggered (still active) and has
been acknowledged
36
Not Triggered Not Acked – Alarm no longer appears
(inactive) but not acknowledged
Not Triggered Acked – Alarm no longer appears
(inactive) and acknowledged
Not Triggered – Alarm no longer appears (inactive),
acknowledged, and reset (removed from Active Alarms
list)
State
Alarm is Active (Triggered) if State Value = 1 (still active in
the PLC)
Alarm is Not Active (Not Triggered) if State Value = 0 (can
be reset using Reset button)
Both Active and Non Active alarms can be acknowledged.
When a Non Active alarm is acknowledged, it can be reset
which will remove it from the list to show only Active alarms
in the list.
Description
This column provides alarm description or for certain
alarms, snapshots of module parameters values.
Alarms Filtering
State Filter applies to Alarm State.
Alarm State '0' – Alarm is inactive.
Alarm State '1' – Alarm is active (even if it has been
acknowledged).