Table 15. Interface panel diagnostic code key (continued)
Compressor 1 External Fault
CoreSense 1 Warning
CoreSense 1 Fault
CoreSense 1 Failure
CoreSense 1 Lockout
CoreSense 1 Offline
Compressor 2 External Fault
CoreSense 2 Warning
CoreSense 2 Fault
CoreSense 2 Failure
CoreSense 2 Lockout
CoreSense 2 Offline
ABB VFD 1 Warning
ABB VFD 1 Fault
ABB VFD 1 Lockout
ABB VFD 1 Offline
ABB VFD 2 Warning
ABB VFD 2 Fault
ABB VFD 2 Lockout
ABB VFD 2 Offline
Evaporator Freezing Alarm
Phase Monitor Alarm
Evaporator Flow Alarm
Condenser Flow Alarm
HP Alarm
HP Switch Alarm
LP Alarm
LP Lockout Alarm
Secondary 1 communication
lost
Secondary 2 communication
lost
Secondary 3 communication
lost
Secondary 4 communication
lost
Secondary 5 communication
lost
Secondary 6 communication
lost
Secondary 7 communication
lost
ARTC-SVX008A-EN
Shuts down compressor 1
Auto Reset
Warning
Auto Reset
Shuts down compressor 1
User Reset
Shuts down compressor 1
User Reset
User Reset
Shuts down Circuit 1
Shuts down compressor 1
Auto Reset
Shuts down compressor 2
Auto Reset
Warning
Auto Reset
Shuts down compressor 2
User Reset
Shuts down compressor 2
User Reset
User Reset
Shuts down Circuit 2
Shuts down compressor 2
Auto Reset
Warning
Auto Reset
Shuts down compressor 1
User Reset
Shuts down compressor 1
User Reset
Shuts down compressor 1
Auto Reset
Warning
Auto Reset
Shuts down compressor 2
User Reset
Shuts down compressor 2
User Reset
Shuts down compressor 2
Auto Reset
User Reset
Locks out module
Shuts down chiller bank
Auto Reset
Locks out module
User Reset
Shuts down Circuits
User Reset
Shuts down Circuits/Circuit 1
User Reset
User Reset
Shuts down Circuit 1/2
Auto Reset
Shuts down Circuit 1/2
Auto Reset
Shuts down Circuit 1/2
User Reset
Shuts down Circuit 1/2
Warning
Auto Reset
Warning
Auto Reset
Warning
Auto Reset
Warning
Auto Reset
Warning
Auto Reset
Warning
Auto Reset
Warning
Auto Reset
(e)
(f)
(g)
(g)
Chiller Troubleshooting
67