Optional Variable Frequency Drive
Table 18. Warning and alarm definitions and troubleshooting (continued)
Warning/Alarm
Description / Probable Cause
WARNING 62,
The output frequency has reached the value
Output frequency at
set in 4-19 Max Output Frequency.
maximum limit
WARNING/ALARM
The cut-out temperature of the control card is
65, Control card over
80 °C.
temperature
The frequency converter is too cold to
WARNING 66,
operate. This warning is based on the
Heatsink temperature
temperature sensor in the IGBT module.
low
ALARM 67, Option
One or more options have either been added
module configuration
or removed since the last power-down.
has changed
ALARM 69, Power
The temperature sensor on the power card is
card temperature
either too hot or too cold
ALARM 70, Illegal FC
The control card and power card are
configuration
incompatible.
ALARM 78, Tracking
Parameter settings are initialized to default
error Drive initialized
settings after a manual reset.
to default value
A no-flow condition has been detected in the
ALARM 92, No flow
system. 22-23 No-Flow Function is set for
alarm.
A no-flow condition in the system with the
ALARM 93, Dry
frequency converter operating at high speed
pump
may indicate a dry pump. AP-26 Dry Pump
Function is set for alarm.
Feedback is lower than the set point. This
ALARM 94, End of
may indicate leakage in the system. 22-50
curve
End of Curve Function is set for alarm.
Torque is below the torque level set for no
ALARM 95, Broken
load, indicating a broken belt. 22-60 Broken
belt
Belt Function is set for alarm.
Motor start has been delayed due to short-
ALARM 96, Start
cycle protection. 22-76 Interval between
delayed
Starts is enabled.
Stopping the motor has been delayed due to
WARNING 97, Stop
short cycle protection. 22-76 Interval between
delayed
Starts is enabled.
WARNING 98, Clock
Time is not set or the RTC clock has failed.
fault
This warning indicates the frequency
WARNING 200, Fire
converter is operating in fire mode. The
mode
warning clears when fire mode is removed.
WARNING 201, Fire
This indicates the frequency converter had
mode was active
entered fire mode.
While operating in fire mode one or more
WARNING 202, Fire
alarm conditions have been ignored which
mode limits
would normally trip the unit. Operating in this
exceeded
condition voids unit warranty.
A–8
Troubleshooting
Check the application to determine the cause. Possibly increase the output frequency
limit. Be sure the system can operate safely at a higher output frequency. The warning
will clear when the output drops below the maximum limit.
Check that the ambient operating temperature is within limits.
Check for clogged filters.
Check fan operation.
Check the control card.
Increase the ambient temperature of the unit. Also, a trickle amount of current can be
supplied to the frequency converter whenever the motor is stopped by setting 2-00 DC
Hold/Preheat Current at 5% and 1-80 Function at Stop
Check that the configuration change is intentional and reset the unit.
Check that the ambient operating temperature is within limits.
Check for clogged filters.
Check fan operation.
Check the power card.
Contact your supplier with the type code of the unit from the nameplate and the part
numbers of the cards to check compatibility.
Reset the unit to clear the alarm.
Troubleshoot the system and reset the frequency converter after the fault has been
cleared.
Troubleshoot the system and reset the frequency converter after the fault has been
cleared.
Troubleshoot the system and reset the frequency converter after the fault has been
cleared.
Troubleshoot the system and reset the frequency converter after the fault has been
cleared.
Troubleshoot the system and reset the frequency converter after the fault has been
cleared.
Troubleshoot the system and reset the frequency converter after the fault has been
cleared.
Reset the clock in 0-70 Date and Time.
See the fire mode data in the alarm log.
Cycle power to the unit to remove the warning. See the fire mode data in the alarm log.