Specifications - Dometic 59530 Series Manual

Roof top air conditioner
Table of Contents

Advertisement

Model
Nominal
Electrical
Number
Capacity
Rating
(BTU/HR
Cooling
59530.542
N/A
120VAC
60Hz.
1 Phase
*
For wire length over 24 ft., consult the National Electric Code for proper sizing.
**
Dometic, LLC gives GENERAL guidelines for generator requirements. These guidelines come from experiences people have had in actual ap-
plications. When sizing the generator, the total power usage of your recreational vehicle must be considered. Keep in mind generators lose power
at high altitudes and from lack of maintenance.
*** CIRCUIT PROTECTION: Time Delay Fuse or HACR Circuit Breakers Required.
1. PRECAUTIONS
Improper installation may damage equipment,
could endanger life, cause serious injury and/
or property damage.
A. Read installation and operating instructions carefully
before attempting to start your unit installation.
B. The Dometic, LLC will not be liable for any dam-
ages or injury incurred due to failure in following
these instructions.
C. Installation must comply with the National Electri-
cal Code and any State or Local Codes or regula-
tions.
D. DO NOT add any devices or accessories to this unit
except those specifi cally authorized by Dometic.
E. This equipment must be serviced by qualifi ed
personnel and some states require these people
to be licensed.
2. CHOOSING LOCATION FOR THE
UNIT
This unit is specifi cally designed for installation on the
roof of a recreational vehicle (RV).
A. NORMAL LOCATIONS:
1. The unit is designed to fi t over an existing roof
vent opening. When the vent is removed,
it normally creates a 14-1/4" x 14-1/4" ±1/8
opening.
2. It is preferred that this unit be installed in a
relatively fl at and level roof section measured
with the RV parked on a level surface; however,
o
up to 15
slant to either side, or front-to-back,
is acceptable.
B. OTHER LOCATIONS:
When no roof vent is available or another location
is desired, the following is recommended:
1. For one unit installation: The unit should be
mounted slightly forward of center (front to
back) and centered from side to side.
2. For two unit installations: Install one units 1/3
and one unit 2/3's from front of RV and centered
from side to side.

SPECIFICATIONS

Compressor
Compressor
Fan Motor
Rated
Locked
Rated
Load
Rotor
Load
Amps
Amps
Amps
8.0
53.0
2.5
59530 SERIES INSTALLATION AND OPERATING INSTRUCTIONS
Fan Motor
Refrigerant
Minimum
Locked
R-22
Wire
Rotor
(Oz.)
Size*
Amps
5.8
16.0
12 AWG
Copper
Up To 24'
It is the responsibility of the installer of this
unit system to ensure structural integrity of
the RV roof. Never create a low spot on the
roof where water will collect. Water standing
around the unit may leak into the interior
causing damage to the product and the RV.
C. AFTER LOCATION SELECTION:
1. Check for obstructions in the area where unit
will be installed.
2. The roof must be designed to support 130
pounds when the RV is in motion. Normally a
200 lb. static load design will meet this require-
ment.
3. Check inside the RV for air box obstructions.
(i.e. door openings, room dividers, curtains,
ceiling fi xtures, etc.) See FIG. 1 & 2.
FIG. 1
Rear
Of Unit
3
AC Circuit
Installed
Protection
Weight
*** User
(Pounds)
Supplied
15 Amp
93
18"
Keep This Area Free From Obstructions
Dimensions Are Nominal
Minimum Generator
Size**
1 Unit/2 Units
2.5 KW / 4.0 KW
14-1/4" x 14-1/4"
Opening

Advertisement

Table of Contents
loading

This manual is also suitable for:

59530.5423107211