11

Connecting the power cords

Use the following information to connect the power cords in your storage array.
11.1
Things to know – AC power cords
Observe the following:
11.2
Procedure – connecting AC power cords
To connect AC power cords:
1.
2.
3.
4.
5.
2016.12 | V2.1 | DOC
For each AC power connector on the drive tray, make sure that you use a separate power
source in the cabinet. Connecting to independent power sources maintains power
redundancy.
To ensure proper cooling, do not operate a drive tray with one of its power supplies
removed.
You can use the power cords shipped with the controller-drive tray with typical outlets
used in the destination country, such as a wall receptacle or an uninterrupted power
supply (UPS). These power cords, however, are not intended for use in most EIA-
compliant cabinets.
Make sure that the circuit breakers in the cabinet are turned off.
Make sure that both of the Power switches on the controller-drive tray are turned off.
1 - Power switches
Connect the primary power cords from the cabinet to the external power source.
Connect a cabinet interconnect power cord (or power cords specific to your particular
cabinet) to the AC power connector on each power canister in the drive tray.
If you are installing other drive trays in the cabinet, connect a power cord to each power
canister in the drive trays.
Port 1
Port 2
Lnk
Lnk
iSCSI
Host
Lnk
Lnk
L
S
S
L
Drive Expansion
S
A
S
Installation manual
DSA E-Series (E2700)
Port 1
Port 2
Lnk
iSCSI
Host
Lnk
L
S
S
L
Drive Expansion
S
A
S
1
49002-02
Bosch Sicherheitssysteme GmbH
Lnk
Lnk

Advertisement

Table of Contents
loading

Table of Contents