Program Dry Operation - Daikin FTKM-U Series Service Manual

Inverter pair wall mounted type r-32
Table of Contents

Advertisement

Main Functions
1.6

Program Dry Operation

Outline
Program dry operation removes humidity while preventing the room temperature from lowering.
Since the microcomputer controls both the temperature and airflow rate, the temperature
adjustment and FAN setting buttons are inoperable.
Details
The microcomputer automatically sets the temperature and airflow rate. The difference between
the room thermistor temperature at start-up and the target temperature is divided into two
zones. Then, the unit operates in an appropriate capacity for each zone to maintain the
temperature and humidity at a comfortable level.
temperature at start-up
 Thermostat turns on also when the room temperature is in the zone B for 10 minutes.
30
Room temperature
X – 1.0°C
Y = X – 2.5°C
or
Y = X – 2.0°C
Room thermistor
Target temperature
24°C or more
Room thermistor
temperature at start-up
18 ~ 23.5°C
17.5°C or less
Room temperature
Zone C = Thermostat ON
Zone B
Zone A = Thermostat OFF
Thermostat OFF point
X
18°C
X – 2.0°C = 16°C
Target temperature X
Z = X – 0.5°C
(R22443)
Thermostat ON point
Y
X – 2.5°C
X – 0.5°C
X – 2.0°C
X – 0.5°C
X – 0.5°C = 17.5°C
Part 4 Functions and Control
SiMX042215E
Z 

Advertisement

Table of Contents
loading

Table of Contents