Input Overcurrent Detection - Daikin FTKM-U Series Service Manual

Inverter pair wall mounted type r-32
Table of Contents

Advertisement

Troubleshooting

4.14 Input Overcurrent Detection

E8
Error Code
Method of Error
An input overcurrent is detected by checking the input current value with the compressor
Detection
running.
Error Decision
The current exceeds 7 ~ 10 A (depending on the model) for 2.5 seconds with the compressor
Conditions
running.
The upper limit of the current decreases when the outdoor temperature exceeds a certain level.
Supposed
 Outdoor temperature out of operation range
Causes
 Defective compressor
 Defective power module
 Defective outdoor unit PCB
 Short circuit
Troubleshooting
Reference
Check No.15 Refer to P.93
Reference
Check No.17 Refer to P.96
Reference
Check No.18 Refer to P.96
74
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
An input overcurrent may result from wrong internal wiring. If the system is interrupted by an input overcurrent
after the wires have been disconnected and reconnected for part replacement, check the wiring again.
Check No. 17
Check the installation condition.
Start operation and measure the
input current.
Input current flowing
above its stop level?
YES
Turn off the power and disconnect
the harnesses U, V, and W.
Check No. 15
Check with the inverter analyzer.
Any LED off?
NO
Turn off the power, and reconnect
the harnesses. Turn on the power
again and start operation.
Check No. 18
Check the discharge pressure.
NO
Inverter analyzer:
RSUK0917C
YES
SiMX042215E
Replace the outdoor unit
PCB (main PCB).
Correct the power supply
or replace the outdoor unit
PCB (main PCB).
(R21863)