Daikin FTKM-U Series Service Manual page 69

Inverter pair wall mounted type r-32
Table of Contents

Advertisement

SiMX042215E
Troubleshooting
Check the connection of the
compressor harness.
Part 6 Service Diagnosis
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Check the power supply voltage.
Is the
voltage fluctuation
within ±10% from the
rated value?
YES
Loose or
disconnected?
NO
Does the
outdoor fan rotate
smoothly?
YES
Turn on the power.
System
restarted? (Repeat a few
times.)
NO
Error
again within 3 minutes
after turning on the
power?
YES
NO
YES
NO
(Precaution before turning on the power
again) Make sure the power has been off
for at least 30 seconds.
Disturbance factors
YES
∗ Noise
∗ Power supply distortion
NO
Troubleshooting
Correct the power supply.
Reconnect the harness.
Replace the outdoor fan motor
and the outdoor unit PCB
(main PCB).
Check for such factors for a
long term.
Replace the outdoor
unit PCB (main PCB).
Replace the indoor
unit PCB (control PCB).
(R24749)