3.9

F: Options

F1: Fault Detection in PG Speed Control

No.
Name
(Hex.)
F1-02
Encoder Signal Loss Detect
Sel
(0381)
F1-03
Overspeed Detection
Selection
(0382)
F1-04
Speed Deviation Detection
Select
(0383)
F1-08
Overspeed Detection Level
(0387)
F1-09
Overspeed Detection Delay
Time
(0388)
F1-10
Speed Deviation Detection
Level
(0389)
F1-11
Speed Deviation Detect
DelayTime
(038A)
F1-14
Encoder Open-Circuit Detect
Time
(038D)
YASKAWA TOEPYAIGA5001A GA500 DRIVE MAINTENANCE & TROUBLESHOOTING
Sets the method to stop the motor or let the motor continue operating when the drive detects PGo
[Encoder (PG) Feedback Loss].
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : No Alarm Display
Note:
When A1-02 = 0 [Control Method Selection = V/f], set H6-01 = 3 [Terminal RP Pulse Train
Function = Speed Feedback (V/F Control)] to enable this parameter.
Sets the method to stop the motor or let the motor continue to operate when the drive detects oS
[Overspeed].
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
Note:
When A1-02 = 0 [Control Method Selection = V/f], set H6-01 = 3 [Terminal RP Pulse Train
Function = Speed Feedback (V/F Control)] to enable this parameter.
Sets the method to stop the motor or let the motor continue to operate when the drive detects dEv
[Speed Deviation].
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
Note:
When A1-02 = 0 [Control Method Selection = V/f], set H6-01 = 3 [Terminal RP Pulse Train
Function = Speed Feedback (V/F Control)] to enable this parameter.
Sets the detection level of oS [Overspeed] as a percentage when the maximum output frequency is
100%.
Note:
• Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output
frequency.
–A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
–A1-02 = 8: E9-02 [Motor Max Revolutions]
• When A1-02 = 0 [Control Method Selection = V/f], set H6-01 = 3 [Terminal RP Pulse Train
Function = Speed Feedback (V/F Control)] to enable this parameter.
Sets the length of time that the speed feedback must be more than the F1-08 level to cause oS
[Overspeed].
Note:
When A1-02 = 0 [Control Method Selection = V/f], set H6-01 = 3 [Terminal RP Pulse Train
Function = Speed Feedback (V/F Control)] to enable this parameter.
Sets the detection level of dEv [Speed Deviation] as a percentage when the maximum output
frequency is 100%.
Note:
• Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output
frequency.
–A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
–A1-02 = 8: E9-02 [Maximum Speed]
• When A1-02 = 0 [Control Method Selection = V/f], set H6-01 = 3 [Terminal RP Pulse Train
Function = Speed Feedback (V/F Control)] to enable this parameter.
Sets the length of time that the difference between the frequency reference and speed feedback must
be more than the level in F1-10 to cause dEv [Speed Deviation].
Note:
When A1-02 = 0 [Control Method Selection = V/f], set H6-01 = 3 [Terminal RP Pulse Train
Function = Speed Feedback (V/F Control)] to enable this parameter.
Sets the length of time that the drive must not receive a pulse signal to cause PGo [Encoder (PG)
Feedback Loss].
Note:
Motor speed and load conditions can cause ov [Overvoltage] and oC [Overcurrent] faults.
When A1-02 = 0 [Control Method Selection = V/f], set H6-01 = 3 [Terminal RP Pulse Train
Function = Speed Feedback (V/F Control)] to enable this parameter.
Description

3.9 F: Options

Default
(Range)
1
(0 - 4)
1
(0 - 3)
3
(0 - 3)
115%
(0 - 120%)
Determined by A1-02
(0.0 - 2.0 s)
10%
(0 - 50%)
3
0.5 s
(0.0 - 10.0 s)
2.0 s
(0.0 - 10.0 s)
119