3.5 Analog Output Functions
3.5.2 Analog Output Range Setting
When a set value is entered in the "Output range setting area" using the user program, the
analog output range is set in the unit
● When H1 to H7 is entered in the "Output range setting area", the analog output is started.
● If a change is made to the program after the mode is changed to the PROG. mode, cycle the
power.
■
Sample program
If an expansion is made to the 1st unit, set as follows using the user program to set the -10 to
+10 V range to CH0 and CH1 and the +4 to +20 mA range to CH2 and CH3.
R0
■
Output range setting value
H1: 0 to +10 V
H2: 0 to +5 V
H3: 0 to +20 mA
H4: -10 to +10 V
H5: -5 to +5 V
H6: +1 to +5 V
H7: +4 to +20 mA
H0, H8 to F: Do not use the analog input.
■
I/O allocation
Channel
CH0 to CH3
■
I/O contents
The range setting data for each channel data is allocated from the lower level in the order of
CH0, CH1, CH2, and CH3.
3-18
F0 MV
Expansion location
1st unit
2nd unit
3rd unit
WY36
WY46
WY56
H7744
WY36
4th unit
5th unit
6th unit
WY66
WY76
WY86
7th unit
8th unit
WY96
WY106
WUME-FPXHAIO-01