Enabling Averaging Processing Setting - Panasonic AFPXHEAD4 User Manual

Programmable controller fp-xh expansion analog unit
Table of Contents

Advertisement

● When the number of retrieved analog input data has reached the set number of averaging
times (64 times or 128 times), averaging is performed for the number of times and the results
are stored as digital values.
● If the number of retrieved data is less than the set number of averaging times, the data
retrieved for the first time is stored in the external input area (WX).
(Note 1)
To make the explanation simple, the above figure shows the processing which averages five points. In
the actual processing, calculation is carried out with the average of data for 64 times or 128 times.
Method for setting the number of averaging times
The number of averaging times can be changed by being written to the output relay area (WY)
in a user program.

5.1.3 Enabling Averaging Processing Setting

The averaging method can be specified for each channel by changing "Averaging processing
setting" using a user program.
Applicable model
Model
AFPXHAD4
AFPXHAD8
AFPXHA21
Averaging processing setting
H1: Moving average 10 times (Maximum and minimum values are deleted.)
H2: No. of averaging times: 64 times
H3: No. of averaging times: 128 times
WUME-FPXHAIO-01
5.1 Analog Input Average Processing
Channel
CH0 to CH3
CH0 to CH7
CH0 to CH1
5-3