Disconnection Detection - Panasonic AFPXHEAD4 User Manual

Programmable controller fp-xh expansion analog unit
Table of Contents

Advertisement

5.2 Disconnection Detection

Digital conversion values corresponding to the analog input are stored.
Applicable model
Model
AFPXHEAD4
AFPXHEAD8
AFPXHEA21
Disconnection detection
● The disconnection detection is valid only when the analog input range setting is set to +4 to
+20 mA or +1 to +5 V.
● If a disconnection state is detected, H8000 (K-32768) is stored in the "Analog input value"
area.
● The detection level for disconnection detection is as follows.
Input range
For +1 to +5 V
For +4 to +20 mA
WUME-FPXHAIO-01
5.2 Disconnection Detection
Channel
CH0 to CH3
CH0 to CH7
CH0 to CH1
Detection level
0.7 V or less
2.8 mA or less
5-5

Advertisement

Table of Contents
loading

This manual is also suitable for:

Afpxhead8Afpxheda4Afpxhea21

Table of Contents