Current Input range: +4 to +20 mA
WUME-FPXHAIO-01
4.1 Input Conversion Characteristics
Input range: +4 to +20 mA
Analog input
value
(mA)
+20
+16
+12
+8
+4
0
When exceeding the rated range
Analog input
value
+20 mA or more
+4 mA or less
Digital conversion
value
(K)
+25,600
+19,200
+12,800
+6,400
0
0
Converted value
+25,600
0