Applicable model
Model
AFPXHEAD4
AFPXHEAD8
AFPXHEA21
■
Input range setting
H1: 0 to +10 V
H2: 0 to +5 V
H3: 0 to +20 mA
H4: -10 to +10 V
H5: -5 to +5 V
H6: +1 to +5 V
H7: +4 to +20 mA
H0, H8 to F: Do not use the analog input.
■
I/O allocation
Channel
Input range setting
area 1
CH0 to CH3
Input range setting
area 2
CH4 to CH7
■
I/O contents
Input range setting area 1
The range setting data for each channel data is allocated from the lower level in the order of
CH0, CH1, CH2, and CH3.
Input range setting area 2
The range setting data for each channel data is allocated from the lower level in the order of
CH4, CH5, CH6, and CH7.
WUME-FPXHAIO-01
Expansion location
1st unit
2nd unit
3rd unit
WY30
WY40
WY50
WY31
WY41
WY51
3.3 Stored Data of the Output Contact (WY)
Channel
CH0 to CH3
CH0 to CH7
CH0 to CH1
4th unit
5th unit
WY60
WY70
WY61
WY71
6th unit
7th unit
8th unit
WY80
WY90
WY100
WY81
WY91
WY101
3-9