Cybersecurity
Security log file
The first time you store a SCF file, ION Setup creates a security log file (SECURITY.LOG) in the
\Security folder.
The security log file contains the history of security configuration files saved from ION Setup.
Use SECURITY.LOG to track meter security configuration changes and to select the correct SCF
file for a meter whose security settings you want to edit or use in another meter.
NOTE: The security log file is stored as plain text.

Disabling and enabling protocols and changing port numbers

Disable unnecessary and unused communication protocol ports—such as SFTP, standard ION
protocol, and network ports—to reduce the meter attack surface. Change port number default
values to reduce the predictability of port use. See
defaults.
Leave Secure ION enabled for configuration changes and upgrades. If Secure ION is disabled,
use the display, Modbus programming, or webpages to access the meter.
Prerequisites:
• Meter connection using ION Setup.
• Login credentials.
• Security configuration access privileges.
LOSS OF ACCESS
Failure to follow these instructions can result in loss of access to the device.
Ensure you maintain sufficient access to communicate with and configure your device.
To disable and enable protocols and change port numbers:
1. In ION Setup, select the meter, and then open Setup Assistant.
2. Click Communications > Advanced Ethernet > Protocols.
3. Select the protocol, and then click Edit.
4. Change the default port number.
5. Enable or disable the protocol.
6. Click OK.
7. Click Exit.
43
"Protocols, ports and connections"
NOTICE
9810 series - User manual
for port
7EN05-0390-08