Using The Phasor Viewer; Basic Setup Using The Webpages Or Display - Siemens US2:9810T24V User Manual

Table of Contents

Advertisement

9810 series - User manual
1
Demo mode is for demonstration only, and does not use the meter input terminals to display
values.

Using the Phasor Viewer

Phasor diagrams can help verify or troubleshoot issues with voltage and current input wiring.
Use ION Setup's Phasor Viewer to display a real-time phasor diagram of the voltage and current
input signals.
To use the Phasor Viewer:
1. Start ION Setup and open the Setup Assistant for your meter.
2. Click Metering Setup > Phasor.
3. Select Phasor Viewer and click Show.
4. To change the polarity of the voltage or current inputs, click Show Setup to display the
Polarity Settings.
Select the box beside the input you want to invert polarity, then click Apply to Meter.

Basic setup using the webpages or display

You can use the meter webpages or display to configure basic metering parameters.
• Using the webpages: Navigate to Setup > Metering.
• Using the display: Navigate to Setup Menu > Meter Setup.
7EN05-0390-08
Parameter
Values
I5 Sec
1–999,999
Scale Rev
ON, OFF
Param
Installation and commissioning
Description
I5 current transformer's secondary winding
current rating
Specifies whether revenue readings are
presented as primary or secondary side values
(ON = primary side, OFF = secondary side)
69

Advertisement

Table of Contents
loading

Table of Contents