Logging
3. Click Logging > Memory screen.
The Status tab:

Log depth configuration

You can change the number of records (depth) stored in the log.
Use ION Setup to change the maximum number of records (depth) stored in the log in the meter's
long-term memory.
Data logs and circular-format waveform recorders have a minimum depth of 1 record. The
maximum depth is dependent on your meter's memory and the configuration of your other logs.

Log interval configuration

You can configure the logging interval, which is how frequently records are logged.
You can change the logging intervals for most logs using the ION Setup Assistant Logging >
Memory screen.
Changing the interval for other logs (for example, logs that are related to standards or triggered by
disturbances) is an advanced procedure that involves using the Advanced mode of ION Setup to
modify settings in the module that is linked to the log's Record input. See the ION Setup help and
the ION Reference for more information.
Programming your meter to write to any data recorder at continuous intervals shorter than 60
seconds (heavy logging configuration) can cause loss of data in the event of a power failure.
DATA LOSS
Failure to follow these instructions can result in data loss.
Use an uninterruptible power supply (UPS) if you program your meter for heavy logging.

Log mode configuration

You can configure the log record mode, or how the log behaves when full.
Changing how the log records information (circular or stop-when-full) is an advanced procedure
that requires changing the RecordMode setup register in the Data Recorder and Waveform
Recorder modules.
233
Lists the default logs, their interval (Duration) and depth (Records), if applicable, and
the percentage of available memory used by the log.
Provides information on how much of the meter's memory is used for system tasks in
the System Resources list item.
Displays the total meter memory and the percentage of memory in use versus memory
available.