Loss Log; Harmonics Logs - Siemens US2:9810T24V User Manual

Table of Contents

Advertisement

9810 series - User manual
Vll ab low
Vll bc low
Vll ca low
Vll avg low

Loss Log

The Loss Log (Data Rec 9) is configured to record loss values.
Factory settings for this data recorder:
• Log depth = 3360 records (35 days)
• Interval = 900 seconds (15 minutes)
By default, it logs the following values:
Parameter
MU Ia^2h int
MU Ib^2h int
MU Ic^2h int
MU Vllab^2h int
MU Vllbc^2h int
MU Vllca^2h int
MU Vln a^2h int
MU Vln b^2h int
MU Vln c^2h int

Harmonics logs

Two harmonics logs record various harmonics data, including K-factor and Total Harmonic
Distortion (THD). These recorders are labeled Harm Mean Log and Harm High Log.
Factory settings for these data recorders:
• Log depth = 840 records (35 days)
• Interval = 3600 seconds (1 hour)
By default, they log the following values:
V1 THD mean
V2 THD mean
V3 THD mean
7EN05-0390-08
Hist Low Log (Data Rec 4)
V unbal low
I avg low
Ia low
I 4 low
Ib low
kW tot low
Ic low
kVAR tot low
Description
Phase A interval current squared hours
Phase B interval current squared hours
Phase C interval current squared hours
Phase A interval voltage Line-to-Line squared hours
Phase B interval voltage Line-to-Line squared hours
Phase C interval voltage Line-to-Line squared hours
Phase A interval voltage Line-to-Neutral squared hours
Phase B interval voltage Line-to-Neutral squared hours
Phase C interval voltage Line-to-Neutral squared hours
Harm Mean Log (Data Rec 7)
I1 THD mean
I2 THD mean
I3 THD mean
Logging
kVA tot low
PF lag low
PF lead low
Freq low
I1 K Fac mean
I2 K Fac mean
I3 K Fac mean
220