8 - DIAGNOSTICS

8.6 - Alarms description

8.6.1 - Alarms list
No.
Code
Description
Thermistor failure
Water Exchanger Entering Fluid Thermistor
1
15001
Failure
Water Exchanger Leaving Fluid Thermistor
2
15002
Failure
3
15003
Circuit A Defrost Thermistor Failure
4
15004
2d Coil Defrost Thermistor Failure
5
15010
OAT Thermistor Failure
MASTER/Slave Common Fluid Thermistor
6
15011
Failure
7
15012
Circuit A Suction Gas Thermistor Failure
8
15024
Circuit A Economizer Gas Thermistor Failure
9
15025
Domestic Hot Water Tank Thermistor Failure
Transducer failure
Circuit A Discharge Pressure Transducer
10
12001
Failure
11
12004
Circuit A Suction Pressure Transducer Failure
12
12013
Circuit A Economizer Pressure Transducer
Water Exchanger Entering Fluid Transducer
13
12024
Failure
Drive failure
14
190nn
Variable Speed Water Pump Failure
Communication failure
Loss of communication with SIOB/CIOB
15
4901
Board Number A
16
4601
Loss of communication with AUX1 Board
Compressor failure
Comp. A1 failed: Motor protection Kriwan
17
1101
Safety Opened
Comp. A2 failed: Motor protection Kriwan
18
1201
Safety Opened
Process failure and other
19
10001
Water Exchanger Freeze Protection
20
10005
Circuit A Low Saturated Suction Temperature
21
10008
Circuit A High Superheat
22
10011
Circuit A Low Superheat
Possible cause
Action taken
Defective thermistor
Unit shuts down
As above
As above
As above
As above
As above
As above
As above
As above
Master/Slave assembly is
As above
disabled
As above
Unit shuts down
As above
As above
As above
DHW mode is disabled
Defective transducer
Unit shuts down
As above
As above
As above
As above
As above
As above
Speed controller fault,
Unit shuts down
see section 8.6.2
Bus installation fault,
Unit shuts down
communication error
As above
Unit shuts down
Compressor
Unit shuts down
overheating
As above
Unit shuts down
No water flow, 
Unit shuts down but the
defective thermistor
pump continues to run
Pressure transducer
defective, EXV blocked
Unit shuts down
or lack of refrigerant
Pressure transducer
defective, temperature
sensor defective,
Unit shuts down
EXV blocked or lack
of refrigerant
As above
Unit shuts down
Reset
Automatic, if thermistor
reading returns to normal
As above
As above
As above
As above
As above
As above
As above
As above
Automatic, if sensor
voltage reading returns to
normal
Automatic, if sensor voltage
reading returns to normal
(up to 3 alarms within 24
hours); otherwise, Manual
Automatic, if sensor
voltage reading returns to
normal
As above
Automatic, if operating
conditions return to normal
Automatic, if communication
is re-established
As above
Manual
Manual
Automatic (the first alarm 
within 24 hours); otherwise,
Manual
As above
Manual
Automatic (up to 3 alarms
within 24 hours); otherwise,
Manual