Carrier SmartVu 61AF 030-105 Manual page 22

Hide thumbs Also See for SmartVu 61AF 030-105:
Table of Contents

Advertisement

5 - USER INTERFACE: MENU STRUCTURE
RESETCFG – Reset Config
No. Name
Status
-20.0 to 51.7
1
oathr_no
-4.0 to 125.0
-20.0 to 51.7
2
oathr_fu
-4.0 to 125.0
0 to 51.7
3
dt_hr_no
0 to 25.0
0 to 13.9
4
dt_hr_fu
0 to 25.0
5
I_hr_no
0 to 20
6
I_hr_fu
0 to 20
-30.0 to 30.0
7
hr_deg
-54.0 to 54.0
*Depends on the selected language (English by default).
CTRLID – Control Identification
No. Status
Default
1
1-239
1
2
0-239
0
3
9600 / 19200 / 38400
9600
4
-
61AF
5
-
-
6
-
-
7
-
-
*Depends on the selected language (English by default).
FLOWCONF – 0-10V Pump Config.
No. Name
Status
1
logictyp
0 to 2
2
minspeed
0 to 45
3
maxspeed
55 to 100
4
step
1 to 20
2.0 to 20.0
5
dt_stp
3.6 to 36.0
0.5 to 2.0
6
deadband
0.9 to 3.6
7
dt_kp
-10 to 10
8
dt_ki
-10 to 10
9
dt_kd
-10 to 10
10 timer
1 to 60
*Depends on the selected language (English by default).
ADD_OPT – Add Options
No. Displayed text*
1
MAC Address
2
Please Enter Your Software Activation Key
3
Unit must be Off
*Depends on the selected language (English by default).
NOTE: If you need to add an option, please contact your local
service representative.
22
Default
Unit
Displayed text*
-10.0
°C
OAT No Reset Value
14.0
°F
-20.0
°C
OAT Full Reset Value
-4.0
°F
0
^C
Delta T No Reset Value
0
^F
0
^C
Delta T Full Reset Value
0
^F
0
mA
Current No Reset Value
0
mA
Current Full Reset Value
10.0
^C
Heating Reset Deg. Value
18.0
^F
Displayed text*
CCN Element Number
CCN Bus Number
CCN Baud Rate
Device Description
Location Description
Software Version
Serial Number
Default
Unit
Displayed text*
0
-
Logic: 0=No,1=STEP,2=PID
10
%
Minimum Pump Speed
100
%
Maximum Pump Speed
5
-
Pump Speed Step
5.0
^C
Water Delta T Setpoint
9.0
^F
1.0
^C
Deadband (for Step ctrl)
1.8
^F
-2
-
PID Control Prop. Gain
-0.2
-
PID Control Integ. Gain
0
-
PID Control Deriv. Gain
10
sec
Reschedule Timer
Description
Controller MAC address: This MAC address is requested by your local service representative
when ordering any software-protected option (see also section 6.13)
Software Activation Key provided by a service technician (see also section 6.13)
The unit should not be operating when installing the Software Activation Key
Description
OAT, no reset value
OAT, max. reset value
Delta T, no reset value
Delta T, max. reset value
Current, no reset value
Current, max. reset value
Heating reset value
Description
Element number
Bus number
Communication speed
Unit description
Location description
Software version
Serial number (MAC address)
Description
Logic type:
0 = No 0-10V external pump
1 = 0-10V External Pump controlled by Step Logic
2 = 0-10V External Pump controlled by PID Logic
Minimum pump speed
Maximum pump speed
Pump speed step
Water delta T setpoint
Deadband for step control
PID control proportional gain
PID control integrative gain
PID control derivative gain
Reschedule timer (delay before the new calculation is made
– used for both Step and PID logic control)