8 - DIAGNOSTICS
No.
Code
Description
23
10014
Cooler Interlock Failure
Compressor A1 Not Started Or Pressure
24
10016
Increase not Established
Compressor A2 Not Started Or Pressure
25
10017
Increase not Established
26
10030
Master/Slave communication Failure
27
10031
Unit is in Network emergency stop
28
10032
Water Pump #1 Fault
Circuit A Repeated High Discharge Gas
29
10037
Overrides
Circuit A Repeated Low Suction Temp
30
10040
Overrides
31
10043
Low Entering Water Temperature In Heating
32
10063
Circuit A High pressure switch Failure
Water Exchanger Temperature Sensors
33
10097
Swapped
Replacement Mode: please contact Service
40
10122
Representative to activate options
41
57001
Circuit A SIOB/CIOB Low Voltage Failure
42
10215
DHW Antilegionella Setpoint Not Achieved
Master/Slave configuration failure
36
9001
Master Chiller Configuration Error
Service and factory
Service Maintenance Alert
01: Service Maintenance Alert
02: Water loop size is low
34
130nn
03: Pump service is required
04: Water filter service
05: Scheduled Service Maintenance date is
near or reached
Fgas check needed, call your maintenance
35
13006
company
37
7001
Illegal Configuration
38
8000
Initial Factory Configuration Required
39
8001
Illegal Brand Identifier
44
Possible cause
Action taken
Interlock input set on
Unit shuts down
Compressor breaker or
fuse fault, compressor
Compressor shuts down
switch open
As above
Compressor shuts down
Bus installation fault,
Master/Slave assembly is
communication error
disabled
Network emergency
Unit shuts down
stop command
Water pump fault
Unit shuts down
Repetitive capacity
No action (alert)
decreases
As above
As above
Low entering fluid 
temperature in
No action (alert)
Heating mode
High pressure switch
No action (alert)
failure
Inlet and outlet
Unit shuts down
temperature reversed
Replacement Mode:
Replacement Mode:
Please contact your
Please contact your local
local service
service representative to
representative to
obtain activation key(s) to
obtain activation key(s)
retrieve (or activate)
to retrieve (or activate)
software options
software options
Supply fault
Unit shuts down
Low OAT
No action (alert)
Master/slave operation is
disabled and the unit
Configuration failure
returns to the stand-alone
mode
Servicing action
Depending on the severity
required / Contact
of the alarm, the unit may
Manufacturer Service
continue to operate or the
Agency
unit shuts down
Maintenance date
No action (alert)
passed
Incorrect unit
Unit cannot be started
configuration
No factory
Unit cannot be started
configuration
Incorrect unit
Unit not allowed to start
configuration
Reset
Automatic (if the unit was
stopped); otherwise,
Manual
Manual
Manual
Automatic, if communication
is re-established
Automatic, if emergency
stop is deactivated
Manual
Automatic (no discharge gas
overrides within 30 min) or
Manual
As above
Automatic, if water
temperature returns to
normal or heating mode is
stopped
Manual
Manual
Automatic, if Software
Activation Key is installed
Automatic, if Software
Activation Key is not
provided within 7 days
since the first compressor 
start (the alarm will be reset
and software-protected
options will be blocked)
Automatic, if supply voltage
returns to normal (up to 6
alarms within 24 hours);
otherwise, Manual
Automatic
Automatic, if master/slave
configuration returns to 
normal or the unit returns
to the standalone mode
Manual (13001-13004) or
Automatic (13005, if the
new maintenance date is
set)
Automatic, if the new
maintenance date is set
Automatic, if configuration is 
corrected
Automatic, if configuration 
is provided
Automatic, if configuration 
is corrected