5 - USER INTERFACE: MENU STRUCTURE
The Main menu provides access to the main control parameters,
including general parameters, inputs and outputs status, etc.
To access the menu, press the Main menu button located in the
upper-left part of the Home screen.
Specific unit parameters can be accessed by pressing the icon 
corresponding to the desired category.
GENUNIT – General Parameters
No. Name
Status
1
CTRL_TYP
0 to 2
2
STATUS
xxx
3
min_left
-
4
SP_SEL
0 to 2
5
6
SP_OCC
no/yes
7
CHIL_S_S
disable/enable
8
CHIL_OCC
no/yes
9
CAP_T
0 to 100
10
DEM_LIM
0 to 100
11
SP
-
26.7 to 65.0
12
CTRL_PNT
80.0 to 149.0
13
CTRL_WT
-
14
EMSTOP
disable/enable
15
ALM
xxx
*Depends on the selected language (English by default).
TEMP – Temperature
No. Name
Status
1
EWT
-
2
LWT
-
3
OAT
-
4
CHWSTEMP
-
5
SCT_A
-
6
SST_A
-
7
SUCT_A
-
8
ECO_SST
-
9
ECO_SUCT
-
10
DEFRT_A
-
11
DEFRT_2
-
12
DHW_TT
-
*Depends on the selected language (English by default).
Unit
Displayed text*
-
Local=0 Net.=1 Remote=2
-
Running Status
min
Minutes Left for Start
-
Setpoint Select
0=Auto. 1=Spt1. 2=Spt2
-
Setpoint Occupied?
-
Net.: Cmd Start/Stop
-
Net.: Cmd Occupied
%
Percent Total Capacity
%
Active Demand Limit Val
°C/°F
Current Setpoint
°C
Control Point
°F
°C/°F
Control Water Temp
-
Emergency Stop
-
Alarm
Unit
Displayed text*
°C/°F
Entering Water Temp
°C/°F
Leaving Water Temp
°C/°F
Outside Air Temperature
°C/°F
Master/Slave Temperature
°C/°F
Saturated Condensing Tp
°C/°F
Saturated Suction Tmp
°C/°F
Suction Gas Temperature
°C/°F
Eco. Saturated Suction T
°C/°F
Economizer Suction Gas T
°C/°F
Defrost Temperature A
°C/°F
Defrost Temp Second Coil
°C/°F
DHW Tank Temperature
NOTE: The Trendings menu is displayed in form of a graph.
For more information about Trendings, see section 6.16.
CAUTION: Since specific units may not include additional
features, some tables may contain parameters that cannot
be configured for a given unit.
Description
Operating mode:
0 = Local, 1 = Network, 2 = Remote
Unit running status:
0 = Off, 1 = Running, 2 = Stopping, 3 = Delay, 4 = Trip out, 
5 = Ready, 6 = Override, 7 = Defrost,
8 = Run Test, 9 = Test
Minutes left before the unit start-up
Setpoint select
0 = Auto, 1 = Setpoint 1, 2 = Setpoint 2
Setpoint occupied?
Unit start/stop via Network: When the unit is in Network mode,
start/stop command can be forced
Unit time schedule via Network: When the unit is in Network
mode, the forced value can be used instead of the real
occupancy state
Total unit capacity
Active demand limit value: When the unit is Network mode, the
minimum value will be used compared to the status of the
external limit switch contact and the demand limit switch
setpoint
Current setpoint
Control point: Water temperature that the unit must produce
Control water temperature
Emergency stop
Alarm status
Description
Entering water temperature: Used for capacity control
Leaving water temperature: Used for capacity control
Outdoor air temperature: Used to determine a number of control
mechanisms such as heat/cool changeover, water exchanger
heater operation, defrost cycle
Master/slave temperature
Saturated condensing temperature
Saturated suction temperature
Suction gas temperature
Economizer saturated suction temperature
Economizer suction gas temperature
Defrost temperature 1 – sensor linked to the first fan
Defrost temperature 2 – sensor linked to the second fan
(only for unit size 75, 105)
Domestic hot water tank temperature