5 - USER INTERFACE: MENU STRUCTURE
DHW_STAT – Domestic Hot Water
No. Name
Status
1
dhw_mode
0 to 2
2
3
dhw_dem
no/yes
4
dhw_ovr
-1 to 100
5
dhw_time
-
6
shc_time
-
7
sum_mode
no/yes
8
ctrl_pnt
-
-40.0 to 115.0
9
DHW_TT
-40.0 to 239.0
10
DHW_REQ
open/close
11
dhw_vlv
open/close
12
leg_hour
-
*Depends on the selected language (English by default).
QCK_TST1 – Quick Test 1
No. Name
Status
1
QCK_TEST
no/yes
2
Q_F_A1LS
off/on
3
Q_F_A1HS
off/on
4
Q_F_A2LS
off/on
5
Q_F_A2HS
off/on
6
Q_EXV_A
0 to 100
7
Q_EXVECO
0 to 100
8
Q_VALV1
off/on
9
Q_VALV2
off/on
10 Q_RV_A
off/on
11 Q_HEAT_A
off/on
12 Q_BOILER
off/on
13 Q_EHS_ST
0 to 4
14 Q_DHWVLV
off/on
15 Q_PUMP1
0 to 2
16 Q_VPUMP1
0 to 100
17 Q_ALARM
off/on
18 Q_RUN
off/on
*Depends on the selected language (English by default).
IMPORTANT: To enable the Quick Test functionality, the unit
must be stopped (Local off mode).
18
Unit
Displayed text*
-
Mode
0=SHC, 1=DHW, 2=AntiLeg
-
DHW Demand
-
DHW Override
min
Current DHW Runtime
min
Current SHC Runtime
-
Summer Active
°C/°F
Control Point
°C
DHW Tank Temperature
°F
-
DHW Request Input
-
Domestic Hot Water Valve
hour
Antileg Last Start Hour
Default
Unit
Displayed text*
no
-
Quick Test Enable
off
-
Fan Stage Circuit A1LS
off
-
Fan Stage Circuit A1HS
off
-
Fan Stage Circuit A2LS
off
-
Fan Stage Circuit A2HS
0
%
Main EXV position
0
%
Economizer EXV Position
off
-
ECO/CPA1 Isolation Valve
off
-
ECO/CPA2 Isolation Valve
off
-
4-Way Refrigerant Valve
off
-
Exchangers Heaters
off
-
Boiler Command
0
-
Electrical Heat Stage
off
-
Domestic Hot Water Valve
0
-
Pump 1 Output
0
%
Variable pump 1
off
-
Alarm Relay Status
off
-
Running Relay Status
Description
Mode
0 = Space Heating Control (SHC)
1 = Domestic Hot Water (DHW)
2 = Anti-Legionella mode
DHW demand
DHW override
Current DHW runtime
Current SHC runtime
Yes = Summer mode active
No = Summer mode not active
Current control point
DHW tank temperature
DHW request input
(used when tank water temperature sensor is not available)
DHW valve output
Number of hours passed since the start of anti-legionella session
(the program cannot be activated more than once within 6 hours)
Description
This parameter is used to enable the Quick Test functionality
(Quick test Enable = yes)
With Quick Test enabled: Forcing a specific parameter given 
in this table allows the user to verify if the component
behaves correctly
Fan stage A1 low speed output, circuit A
Fan stage A1 high speed output, circuit A
Fan stage A2 low speed output, circuit A
Fan stage A2 high speed output, circuit A
Main EXV position
Economizer EXV Position
ECO/CPA1 Isolation Valve
ECO/CPA2 Isolation Valve
4-Way Refrigerant Valve
Exchangers Heaters
Boiler Command
Electric heating command (number of electric heating stages
depends on factory configuration)
Domestic Hot Water Valve
Pump 1 Output
Variable pump 1
Alarm Relay Status
Running Relay Status