5 - USER INTERFACE: MENU STRUCTURE
The Configuration menu gives access to a number of user-
modifiable  parameters  such  as  pump  configuration,  schedule 
menu, etc. The Configuration menu is password-protected.
To access the Configuration menu, press the Main menu button
located in the upper-left part of the Home screen, and then select
Configuration Menu. 
Once all the necessary modifications have been made, press the 
Save button to confirm your changes or the Cancel button to exit
the screen without making modifications.
GENCONF – General Config
No. Name
Status
1
ramp_sel
no/yes
2
off/on_d
1 to 15
*Depends on the selected language (English by default).
PUMPCONF – Pump Configuration
No. Name
Status
1
pump_seq
no/yes
2
pump_per
no/yes
3
pump_loc
no/yes
*Depends on the selected language (English by default).
HCCONFIG – Heat/Cool Config
No. Name
Status
1
hr_sel
0 to 3
2
3
-25.0 to 0.0
4
min_th
-13.0 to 32.0
-100.0 to 100.0
5
max_th
-148.0 to 212.0
-30.0 to 15.0
6
boil_th
-22.0 to 59.0
-5.0 to 21.1
7
ehs_th
23.0 to 70.0
8
ehs_back
no/yes
9
ehs_pull
0 to 60
10 ehs_defr
no/yes
*Depends on the selected language (English by default).
Default
Unit
Displayed text*
no
-
Ramp Loading Select
1
min
Unit Off to On Delay
Default
Unit
Displayed text*
no
-
Exchanger Pump Enable
no
-
Pump Sticking Protection
yes
-
Flow Checked if Pump Off
Default
Unit
Displayed text*
1
-
Heating Reset Select
0=None, 1=OAT
2=Delta T, 3=4-20mA
-20.0
°C
Min Heating OAT Threshld
-4.0
°F
100.0
°C
Max Heating OAT Threshld
212.0
°F
-10.0
°C
Boiler OAT Threshold
14.0
°F
5.0
°C
Elec Stage OAT Threshold
41.0
°F
no
-
1 Elec Stage For Backup
0
min
Electrical Pulldown Time
no
-
Quick EHS For Defrost
System configuration override: In some cases it is possible to
override system configuration. Note that not all parameters can 
be overridden by the control.
CAUTION: Since specific units may not include additional
features, some tables may contain parameters that cannot be
configured for a given unit.
Description
Ramp loading sequence
Unit OFF to ON delay
Description
Water exchanger pump is enabled
Pump anti-sticking protection
Water flow is checked when the pump is off
Description
Heating Reset Select
0 = None, 1 = OAT
2 = Delta T (LWT-EWT)
3 = 4-20 mA control (external temperature sensor)
Minimum OAT threshold (used for unit protection control)
Maximum OAT threshold (used to define the Summer mode)
Boiler OAT threshold
Electric heating stage, OAT threshold
One electric heating stage used for back-up
Electrical pull-down time
Quick EHS for defrost enabled