5 - USER INTERFACE: MENU STRUCTURE
PRESSURE – Pressure
No. Name
Status
1
DP_A
-
2
SP_A
-
3
ECO_SP_A
-
4
5
6
W_P_IN
-
*Depends on the selected language (English by default).
SETPOINT – Setpoint
No. Name
Status
26.7 to 65.0
1
hsp1
80.0 to 149.0
26.7 to 65.0
2
hsp2
80.0 to 149.0
0.1 to 1.1
3
hramp_sp
0.2 to 2.0
4
lim_sp1
0 to 100
*Depends on the selected language (English by default).
INPUTS – Inputs
No. Name
Status
1
ONOFF_SW
open/close
2
SETP_SW
open/close
3
LIM_SW
open/close
4
LIM_ANAL
-
5
FLOW_SW
open/close
6
HP_SW_A
open/close
7
DHW_REQ
open/close
8
FDBK_A1
open/close
9
FDBK_A2
open/close
*Depends on the selected language (English by default).
OUTPUTS – Outputs
No. Name
Status
1
CP_A1
off/on
2
CP_A2
off/on
3
FAN_A1LS
off/on
4
FAN_A1HS
off/on
5
FAN_A2LS
off/on
6
FAN_A2HS
off/on
7
EXV_A
-
8
EXV_ECO
-
9
EV_VALV1
off / on
10
EV_VALV2
off / on
11
RV_A
off/on
12
EXCH_HTR
off / on
13
BOILER
off / on
14
EHS_STEP
0 to 4
16
Unit
Displayed text*
kPa/PSI
Discharge Pressure
kPa/PSI
Main Suction Pressure
kPa/PSI
Eco. Suction Pressure
INTERNAL HYDRONIC MODULE Internal hydronic module
kPa/PSI
Inlet Water Pressure
Default
Unit
Displayed text*
65.0
°C
Heating Setpoint 1
149.0
°F
65.0
°C
Heating Setpoint 2
149.0
°F
0.5
^C
Heating Ramp Loading
1.0
^F
100
%
Switch Limit Setpoint
Unit
Displayed text*
-
Remote On/Off Switch
-
Remote Setpoint Switch
-
Limit Switch
mA
Limit Analog Input
-
Flow Switch
-
HP Switch Circuit A
-
DHW Tank Request
-
CPA1 Safety FeedBack
-
CPA2 Safety FeedBack
Unit
Displayed text*
-
Compressor A1 Output
-
Compressor A2 Output
-
Fan A1LS Output
-
Fan A1HS Output
-
Fan A2LS Output
-
Fan A2HS Output
%
Main EXV Position
%
Economizer EXV Position
-
ECO/CPA1 Isolation Valve
-
ECO/CPA2 Isolation Valve
-
4 Way Refrigerant ValveA
-
Exchangers Heaters
-
Boiler Command
-
Electrical Heat Stage
Description
Compressor discharge pressure
Compressor suction pressure
Economizer suction pressure
Inlet water pressure
Description
Heating setpoint 1 (used during occupied periods)
Heating setpoint 2 (used during unoccupied periods)
Ramp loading setpoint (rate at which the water temperature may
change within one minute)
Setpoint used for capacity limitation
Description
Remote On/Off switch
Remote setpoint switch:
open = setpoint 1
closed = setpoint 2
Demand limit switch
Limit Analog Input 4-20mA
Water exchanger flow switch
High pressure switch, circuit A
Domestic hot water tank request
Compressor A1 safety feedback
(open contact = compressor is stopped)
Compressor A2 safety feedback
(open contact = compressor is stopped)
Description
Compressor A1 status
Compressor A2 status
Fan A1 low speed status
Fan A1 high speed status
Fan A2 low speed status
Fan A2 high speed status
Main EXV position
Economizer EXV position
Economizer / compressor A1 isolation valve
Economizer / compressor A2 isolation valve
4-way refrigerant valve, circuit A: Used to manage cooling /
heating / defrost operation (heat pumps)
Exchanger heater status (used to protect the water
exchanger against freezing in case of low OAT)
Boiler command
Electrical heating stage