5.4

Installer/Servicer notes for the use of light oil with bio blends up to 30%

 When installing the burner, make sure the fuel to be used is
light oil. In the case of light oil with a bio blend up to 30%,
the latter must comply with the manufacturer specifications
(refer to "Technical data" and "Instructions for using biofuel
blends up to 30%").
 If a bio blend is in use the installer must seek information
from the end user that their fuel supplier can evidence that
the blends of fuel conform to the relevant standards.
 Check that the materials used in the construction of the oil
tank and ancillary equipment are suitable for biofuels, If not
these must be upgraded or replaced with bio-compatible
parts.
 Particular attention should be given to the oil storage tank
and supply to the burner. The manufacturer recommends
that existing oil storage tanks are cleaned, inspected and
any traces of water are removed BEFORE biofuel is intro-
duced (contact the tank manufacturer or oil supplier for fur-
ther advice). If these recommendations are not respected
5.5

Operating position

The burner is designed to work only in position 1.
Installation 1 is preferable, as it is the only one that
allows the maintenance operations as described
WARNING
in this manual.
1
20094131
5.6

Burner assembly

The temperature of the incoming air must not
exceed 70 °C.
CAUTION
For correct BF application, the burner must be in-
stalled on an appropriate BF boiler.
WARNING
Installation
2
3
11
GB
this will increase the risk of contamination and possible
equipment failure.
 In line oil filters should be replaced making sure that they are
bio-compatible. The manufacturer recommends a good
quality bio-compatible oil filter at the tank and a secondary
60 micron filter be used to protect the burner pump and noz-
zle from contamination.
 The burner hydraulic components and flexible oil lines must
be suitable for biofuel use (check with the manufacturer if in
doubt).
 The burner must be commissioned and combustion parame-
ters set to appliance manufacturer's recommendations.
 Regularly check visually for any signs of oil leakage from
seals, gaskets and hoses.
 It is strongly recommended that with biofuel use, oil filters
are inspected and replaced every 4 months. More regularly
where contamination is experienced.
Any other positioning could compromise the cor-
rect operation of the appliance.
Installations 2, 3, 4 and 5 are forbidden for safety
WARNING
reasons.