Step Control Of Outdoor Unit Fans - Daikin ERQ Series Service Manual

Condensing unit three phase
Table of Contents

Advertisement

ESiEN09-06 A
2.3

Step Control of Outdoor Unit Fans

Used to control the revolutions of outdoor unit fans in the steps listed in table below, according
to condition changes.
Function
STEP
No.
ERQ 125
0
0
1
285
2
315
3
360
4
450
5
570
6
710
Cooling: 951
7
Heating: 941
Cooling: 951
8
Heating: 941
*
Figures listed above are all those controlled while in standard mode, which vary when the
system is set to high static pressure or capacity precedence mode.
Fan revolutions (rpm)
ERQ 200
ERQ 250
0
0
350
350
370
370
400
400
450
460
540
560
670
680
Cooling: 821
760
Heating: 800
Cooling: 796
Cooling: 821
Heating: 780
Heating: 800