Daikin ERQ Series Service Manual page 142

Condensing unit three phase
Table of Contents

Advertisement

ESiEN09-06 A
c. Monitor mode
To enter the monitor mode, push the
MODE (BS1) button when in
"Setting mode 1".
<Selection of setting item>
Push the SET (BS2) button and set
the LED display to a setting item.
<Confirmation on setting contents>
Push the RETURN (BS3) button to
display different data of set items.
Push the RETURN (BS3) button and
switches to the initial status of
"Monitor mode".
Push the MODE (BS1) button and
returns to "Setting mode 1".
Test Operation
No.
Setting item
0
Various settings
1
C/H unified address
2
Low noise/demand address
3
Not used
4
Airnet address
5
Number of connected AHUs
6
Number of connected BS units
Number of connected zone units
7
(excluding outdoor and BS unit)
8
Number of outdoor units
9
Number of connected BS units
10
Number of connected BS units
Number of zone units (excluding
11
outdoor and BS unit)
12
Number of terminal blocks
13
Number of terminal blocks
Contents of malfunction (the
14
latest)
Contents of malfunction
15
(1 cycle before)
Contents of malfunction
16
(2 cycle before)
20
Contents of retry (the latest)
21
Contents of retry (1 cycle before)
22
Contents of retry (2 cycle before)
Number of multi connection
25
outdoor units
The numbers in the "No." column represent the number of times to press the
SET (BS2) button.
(V2765)
Setting item 0 Display contents of "Number of units for various settings"
EMG operation /
backup operation
setting
Defrost select setting
Te setting
Tc setting
LED display
H1P H2P
H3P
H4P
ON
OFF
Short
Medium
Long
H
M
L
H
M
L
Field Setting
Data display
H5P
H6P
H7P
Lower 4 digits
Lower 6 digits
Lower 4 digits:
upper
Lower 4 digits:
lower
Lower 6 digits
Lower 4 digits:
upper
Lower 4 digits:
lower
Malfunction
code table
Refer page
189.
Lower 6 digits
133