Field Setting
(5) Thermostat Control
(5.1) X-control
When the DDC controller sends a voltage that is lower than 1,5 V, the unit stays thermostat off.
When the voltage is bigger than 1,5 V, the unit goes thermostat on.
(5.2) X-control
When the DDC controller maintains level A for more than B minutes, and the thermostat is on,
thermo off is carried out for at least C minutes. After C minutes, thermostat on-conditions are
checked.
When the DDC controller reaches level D or higher (lower for heating) and the thermostat is off
for at least C minutes (refer to thermo off conditions), thermostat on is carried out for at least E
minutes.
118
Thermo off/on:
Thermo off
Mode n° setting
Setting switch n°
51
Thermo on
Mode n° setting
Setting switch n°
51
Setting position n°
8
00
01
6
00
01
02
03
04
05
06
07
08
09
10
9
00
04
Setting position n°
7
00
02
04
06
08
5
00
01
02
b
00
01
02
03
04
ESiEN09-06 A
Setting
level A = 1 (cooling)
level A = 1 or 2 (cooling)
B = 3 min, C = 3 min
B = 5 min, C = 3 min
B = 7 min, C = 3 min
--
B = 3 min, C = 5 min
B = 5 min, C = 5 min
B = 7 min, C = 5 min
--
B = 3 min, C = 10 min
B = 5 min, C = 10 min
B = 7 min, C = 10 min
level A = 5 (heating)
level A = 4 or 5 (heating)
Setting
D = level 1 (cooling)
D = level 2 (cooling)
D = level 3 (cooling)
D = level 4 (cooling)
D = level 5 (cooling)
E = 3 min
E = 5 min
E = 10 min
D = level 1 (heating)
D = level 2 (heating)
D = level 3 (heating)
D = level 4 (heating)
D = level 5 (heating)