Daikin ERQ Series Service Manual page 36

Condensing unit three phase
Table of Contents

Advertisement

Basic Control
Stand-alone installation
ERQ 125
Notes:
1. INV : Inverter compressor
2. Depending on the operating conditions of compressors, the compressors may run in patterns
26
Compressor Step Control
Compressor operations vary with the following steps.
ERQ 200
STEP
STEP
INV
INV
No.
No.
52 Hz
52 Hz
1
1
56 Hz
56 Hz
2
2
62 Hz
62 Hz
3
3
68 Hz
68 Hz
4
4
74 Hz
74 Hz
5
5
80 Hz
80 Hz
6
6
88 Hz
88 Hz
7
7
96 Hz
96 Hz
8
8
104 Hz
104 Hz
9
9
110 Hz
110 Hz
10
10
116 Hz
116 Hz
11
11
124 Hz
124 Hz
12
12
132 Hz
132 Hz
13
13
144 Hz
144 Hz
14
14
158 Hz
158 Hz
15
15
166 Hz
166 Hz
16
16
176 Hz
176 Hz
17
17
188 Hz
188 Hz
18
18
202 Hz
19
210 Hz
20
218 Hz
21
232 Hz
22
248 Hz
23
266 Hz
24
STD1 : Standard compressor 1
other than those aforementioned.
ERQ 250
STEP
INV
STD1
No.
52 Hz
OFF
1
56 Hz
OFF
2
62 Hz
OFF
3
68 Hz
OFF
4
74 Hz
OFF
5
80 Hz
OFF
6
88 Hz
OFF
7
96 Hz
OFF
8
104 Hz
OFF
9
110 Hz
OFF
10
116 Hz
OFF
11
124 Hz
OFF
12
132 Hz
OFF
13
144 Hz
OFF
14
158 Hz
OFF
15
166 Hz
OFF
16
176 Hz
OFF
17
188 Hz
OFF
18
202 Hz
OFF
19
210 Hz
OFF
20
52 Hz
ON
21
62 Hz
ON
22
68 Hz
ON
23
74 Hz
ON
24
80 Hz
ON
25
88 Hz
ON
26
96 Hz
ON
27
104 Hz
ON
28
116 Hz
ON
29
124 Hz
ON
30
132 Hz
ON
31
144 Hz
ON
32
158 Hz
ON
33
176 Hz
ON
34
188 Hz
ON
35
202 Hz
ON
36
210 Hz
ON
37
ESiEN09-06 A
Function

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents