Combination Table - Daikin ERQ Series Service Manual

Condensing unit three phase
Table of Contents

Advertisement

ESiEN09-06 A

2. Combination Table

Control box
Outdoor unit
EKEQDCBV3 EKEQFCBV3 EKEXV63
three
ERQ125
P
phase
ERQ200
P
ERQ250
P
Heat pump
P: Pair: Combination depending on AHU heat exchanger volume and capacity.
Cap
class
EXV
General Information
P
P
P
-
P
-
Allowed heat exchanger
capacity - COOLING(kW)
Minimum
EKEXV50
5,0
EKEXV63
6,3
EKEXV80
7,9
EKEXV100
10,0
EKEXV125
12,4
EKEXV140
15,5
EKEXV200
17,7
EKEXV250
24,7
EKEXV400
35,4
EKEXV500
49,6
Cooling saturated suction temp. (SST) = 6°C
Air temperature = 27°C DB / 19°C WB
Superheat (SH) = 5 K
Expansion valve kit
EKEXV80 EKEXV100 EKEXV125 EKEXV140 EKEXV200 EKEXV250
P
P
-
P
-
-
Maximum
6,2
7,8
9,9
12,3
15,4
17,6
24,6
30,8
49,5
61,6

Combination Table

P
P
-
P
P
P
P
P
P
Allowed heat exchanger
capacity - HEATING(kW)
Minimum
5,6
7,1
8,9
11,2
13,9
17,4
19,9
27,8
39,8
55,1
Heating saturated suction temp. (SST) = 46°C
Air temperature = 20°C DB
Subcool (SC) = 3 K
-
P
P
Maximum
7,0
8,8
11,1
13,8
17,3
19,8
27,7
34,7
55,0
69,3
5