The normal resistances of the inverter compressor are 0.7-1.5Ω among U V W and infinite between each of U V W and ground. If any of the resistances differ
from these specifications, the compressor has malfunctioned.
2.
The normal resistances of the fan motor coil among U V W are less than 10Ω. If a measured resistance is 0Ω, the fan motor has short-circuited.
3.
Set a multi-meter to buzzer mode and test any two terminals of P U V W of the inverter module. If the buzzer sounds, the inverter module has short-circuited.