Trane 4TVH0086FE000AA Service Manual page 59

Commercial air conditioners
Table of Contents

Advertisement

1.2.2.2 Silent mode setting
In silent mode 1 / 2 / 3 and night silent mode, the outdoor fan speed decreases gradually. In super silent mode 1 / 2 / 3 / 4,
not only the fan speed decreases gradually, but also the compressor frequency decreases gradually.
Table 4-1.3: Silent mode setting
Switch
ENC5
1.2.2.3 Maximum fan speed and capacity output control in different silent mode
Table 4-1.4: Maximum fan speed and capacity output control in different silent modes
ENC5
Switch positions
0
Night silent time is 6h/10h (default)
1
Night silent time is 6h/12h
2
Night silent time is 8h/10h
3
Night silent time is 8h/12h
4
No silent mode
5
Silent mode 1
6
Silent mode 2
7
Silent mode 3
8
Super silent mode 1
9
Super silent mode 2
A
Super silent mode 3
B
Super silent mode 4
Notes:
1.
Fan speed (rpm) for different fan speed index refers to Table 3-5.3 in Part 3, 5.6 "Outdoor Fan Control".
2.
If the system pressure is over 3.5MPa, the system exits silent mode automatically.
Switch positions
5
Silent mode 1 (only limit max. fan speed)
6
Silent mode 2 (only limit max. fan speed)
7
Silent mode 3 (only limit max. fan speed)
8
Super silent mode 1 (limit max. fan speed and compressor frequency)
9
Super silent mode 2 (limit max. fan speed and compressor frequency)
A
Super silent mode 3 (limit max. fan speed and compressor frequency)
B
Super silent mode 4 (limit max. fan speed and compressor frequency)
Description
Description
Max. fan speed index
8-10HP
12HP
14-18HP
28
28
28
30
31
30
28
28
28
26
26
26
24
24
24
28
28
28
27
27
27
26
26
26
25
25
25
58
1
20-22HP
24-26HP
28-32HP
22
28
28
30
30
31
27
28
28
25
26
26
23
24
24
22
28
28
21
27
27
20
26
26
19
25
25
Max.
capacity
output
8-32HP
100%
80%
70%
60%
50%

Advertisement

Table of Contents
loading

Table of Contents