Trane 4TVH0086FE000AA Service Manual page 44

Commercial air conditioners
Table of Contents

Advertisement

4.3 Startup Control for Heating Operation
Table 3-4.2: Component control during startup in heating mode
Component
Inverter compressor A
Inverter compressor B
DC fan motor A
DC fan motor B
Electronic
expansion
valve A
Electronic
expansion
valve C
Four-way valve
Solenoid valve (liquid
refrigerant injection)
Solenoid
valve
(oil
balance)
Solenoid
valve
(fast
defrosting (in heating)
and
unloading
(in
cooling))
Solenoid
valve
(EXV
bypass)
Solenoid valve (indoor
units bypass)
Solenoid valve (inverter
compressor
A
vapor
injection)
Solenoid valve (inverter
compressor
B
vapor
injection)
Solenoid valve (inverter
compressor B pressure
balance)
Wiring
diagram
8-12HP
14-18HP
label
COMP(A)
COMP(B)
FANA
FANB
EXVA
EXVC
ST1
SV2
SV4
SV5
SV6
SV7
SV8A
SV8B
SV9
20-24HP
26-28HP
30-32HP
43
Control functions and states
Controlled according to load requirement,
operating frequency increased by 1 step /
sec
Open once the four-way valve has opened,
controlled according to outdoor ambient
temperature and load requirement
Position (steps) from 0 (fully closed) to 480
or 3000 (fully open), controlled according
to discharge superheat
Position (steps) from 0 (fully closed) to 480
(fully open), controlled according to
temperature different between plate heat
exchanger inlet and outlet
On
Off
Closed for 200 secs, open for 600 secs, then
closed
Open for 4 mins, then closed
Off
Controlled according to load requirement
Controlled
according
compressor A
Controlled
according
compressor B
Open before compressor B startup
to
inverter
to
inverter

Advertisement

Table of Contents
loading

Table of Contents