Trane 4TVH0086FE000AA Service Manual page 100

Commercial air conditioners
Table of Contents

Advertisement

L2: DC bus high voltage protection
L2 protection
The power supply is abnormal
The DC bus voltage (P, N) is abnormal
Replace the inverter module
Note:
1.
The normal DC voltage between terminals P and N on inverter module should be 450-650V. When the voltage is higher than 700V, L2
protection will be appeared.
Yes
No
Yes
1
No
Figure 6-2.7: Inverter module terminals
U V W
Check the power supply
equipment
Replace the 3-phase bridge
rectifier
99
P
P
N

Advertisement

Table of Contents
loading

Table of Contents