1 General Control Scheme Flowchart
Sections 3-2 to 3-7 on the following pages detail when each of the controls in the flowchart below is activated.
Stop operation
Abnormal shutdown
System stops
A unit stops when the load demanded decreases
Standby control
Crankcase heater control
Startup control
Compressor startup delay control
Startup control for cooling operation
Startup control for heating operation
Normal operation control
Component control during normal operation
Compressor output control
Compressor step control
Operation priority and rotation of compressors
Electronic expansion valve control
Outdoor fan control
Protection control
High pressure protection control
Low pressure protection control
Discharge temperature protection control
Compressor and inverter module protection
control
Disable heating control
Thermo on
2
3
4
Thermo on
5
Conditions met
for oil return
Conditions met
for defrosting
6
Legend
40
Special control
Oil return operation
Defrosting operation
Numbers in the top right-hand
corners of boxes indicate the
relevant section of text on the
following pages.
7