2.22 PP: Compressor discharge insufficient superheat protection
Digital display output
Description
Compressor discharge insufficient superheat protection.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition
Trigger condition: Discharge gas superheat is ≤ 0
Recover condition: Discharge gas superheat go back to normal value.
Reset method: Resume automatically.
Possible causes
Temperature sensor not connected properly or has malfunctioned.
Poor temperature sensor heat insulation.
Excess refrigerant.
Discharge pressure too high.
Main PCB damaged.
o
C for 20 minutes or ≤ 5
124
o
C for 60 minutes.