Table 5-2.1: Main PCB ports
Label in
Port code
Figure 5-2.1
1
CN18
2
CN19
3
CN4
4
CN5
5
CN3
6
CN13
7
CN17
8
CN15
9
CN16
10
CN8
11
CN1
12
CN6
13
CN22-CN23
14
CN26
15
CN27
16
CN9
17
CN28
18
CN71
19
CN70
20
CN72
21
CN82
22
CN66-CN67
23
CN47
24
CN80
CN41-CN46;
25
CN83-CN85
26
CN30
Content
High pressure switch and discharge temperature switch(es)
connections
Low pressure switch connection
Compressor top temperature sensor (single compressor
units) or compressor A compressor top temperature sensor
(dual compressor units) connection
Discharge pipe temperature sensor (single compressor units)
or compressor B compressor top temperature sensor (dual
compressor units) connection
Inverter module temperature sensor A connection
Inverter module temperature sensor B connection
High pressure sensor connection
Inverter compressor A and B current sensor connections
Reserved
Plate heat exchanger inlet temperature sensor connection
Outdoor ambient temperature sensor and outdoor heat
exchanger temperature sensor connections
Plate heat exchanger outlet temperature sensor connection
Communication port
Communication port to compressor drive board
Communication port to fan drive board
USB port
Reserved
EEVB drive port
EEVA drive port
EEVC drive port
Control port of relay for AC filter board
Power supply to compressor crankcase heater
Four-way valve drive ports
Alarm signal output port (reserved)
Solenoid valve drive ports
Power input of main board
0V or 5V DC
0V or 5V DC
0-5V DC (varying)
0-5V DC (varying)
0-5V DC (varying)
0-5V DC (varying)
0-5V DC (varying)
0-7.8V AC (varying)
/
0-5V DC (varying)
0-5V DC (varying)
0-5V DC (varying)
2.5-2.7V DC
2.5-2.7V DC
2.5-2.7V DC
2.5-2.7V DC
/
0V or 12V DC
0V or 12V DC
0V or 12V DC
0V or 12V DC
220V AC
220V AC
220V AC
220V AC
220V AC between A/B/C and N;
380V AC between A,B and C