Unit Control Board Flash Codes; Unit Control Board - York ZF 180 Series Installation Manual

Hide thumbs Also See for ZF 180 Series:
Table of Contents

Advertisement

1061903-XIM-A-0713
Table 31: Unit Control Board Flash Codes
FLASH
CODE
On Steady
This is a Control Failure
1 Flash
Not Applicable
2 Flashes
Control waiting ASCD
3 Flashes
HPS1 Compressor Lockout
4 Flashes
HPS2 Compressor Lockout
5 Flashes
LPS1 Compressor Lockout
6 Flashes
LPS2 Compressor Lockout
7 Flashes
FS1 Compressor Lockout
8 Flashes
FS2 Compressor Lockout
9 Flashes
Ignition Control Locked Out / Ignition Control Failure
10 Flashes
Compressors Locked Out on Low Outdoor Air Temperature
Compressors locked out because the Economizer is using free Cool-
11 Flashes
1
ing
12 Flashes
Unit Locked Out due to Fan Overload Switch Failure
13 Flashes
Compressor Held Off due to Low Voltage
14 Flashes
EEPROM Storage Failure
OFF
No Power or Control Failure
1. Non-alarm condition.
Check
Alarm
History
Reset All ASCDs
For One Cycle
Non Alarm Condition
Green LED Flashing
Current Alarm
Flashed Red LED
Figure 32: Unit Control Board
48
DESCRIPTION
1
1
GREEN
RED
LED
LED
16
-
-
Flashing
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
Off
On
1
Flashing
On
Flashing
On
Off
On
Flashing
On
Off
On
Off
Off
RED
RED
LED
LED
8
4
2
-
-
-
-
-
-
Off
Off
On
Off
On
On
Off
Off
On
Off
On
On
Off
On
On
Off
Off
Off
Off
Off
On
Off
On
On
Off
On
Off
On
On
Off
Off
Johnson Controls Unitary Products
RED
LED
1
-
-
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
Off

Hide quick links: