Connecting the Failsafe Alarm Relay

The failsafe relay on the Control Module (CM) can be configured to latch based
on alarm conditions. The NO (Normally Open) contact is closed when the unit is
powered and there are no active alarms. If the device is not powered or if an active
alarm is configured, the relay opens the NO contact and closes the NC (Normally
Closed) contact.
RUGGEDCOM MX5000RE
Equipment Manual, 11/2023, C79000-G8976-1060-17
1
2
3
External Tooth Lock Washer
1
#8-32×5/16" Pan Head Screw
2
Grounding Cable
3
Figure 2.4
Chassis Ground Cable Assembly
Secure the grounding cable and external tooth lock washer to the RUGGEDCOM
MX5000 with one pan head screw. Torque the screw to 3.4 N·m (30 lbf·in).
Note
The other end of the grounding cable will be connected to the inside of the
enclosure in later steps.