1.5.3 Supported fiber optic cables
reliable, error-free data communication, new and pre-existing communication paths
should be verified for TIA/EIA-568-A compliance.
The following table summarizes the relevant cabling standards:
Follow these recommendations for copper data cabling in high electrical noise
environments:
1.5.3
Supported fiber optic cables
The following fiber optic cable types are supported under the stated conditions.
Cable Type
Wavelength (nm) Modal Bandwidth
OM1 (62.5/125)
OM2 (50/125)
a
OM3 (50/125)
a
OM4 (50/125)
a
Laser optimized.
10
Cabling
1000Base-
Category
TX Compliant
< 5
No
5
Yes
5e
Yes
6
Yes
> 6
Yes
Data cable lengths should be as short as possible, preferably 3 m (10
ft) in length. Copper data cables should not be used for inter-building
communications.
Power and data cables should not be run in parallel for long distances, and
should be installed in separate conduits. Power and data cables should intersect
at 90° angles when necessary to reduce inductive coupling.
Shielded/screened cabling can be used when required. Care should be taken to
avoid the creation of ground loops with shielded cabling.
(MHz·km)
850
200
1300
500
850
500
1300
500
850
1500
1300
500
850
3500
1300
500
Required Action
New wiring infrastructure required.
Verify TIA/EIA-568-A compliance.
No action required. New installations should be designed with
Category 5e or higher.
No action required.
Connector and wiring standards to be determined.
100Base-FX
2000
2000
2000
2000
Distance (m)
1000Base-SX
10GBase-SR
275
550
550
550
RUGGEDCOM MX5000RE