Cable Routing In Cable Ducts Or Fan Subassemblies; Routing Fiber-Optic Cables - Siemens SIMATIC S7-400 Installation Manual

Automation system, hardware and installation
Hide thumbs Also See for SIMATIC S7-400:
Table of Contents

Advertisement

Wiring the S7-400
4.22

Cable routing in cable ducts or fan subassemblies

Cable Routing
Depending on the number of cables and plug-in lines merging at the particular
rack, the cross-section of the cable duct or fan subassembly may not be sufficient
to accept all cables.
You should therefore route half the cables toward each side via the cable duct or
fan subassembly.
Securing Cables
There are eyes for securing cables on both sides of the cable duct or fan
subassembly (see Reference Manual Module Specifications , Chapter 6). You can
secure the cables to these eyes with cable ties, for example.
Shield Contact
The cable duct and fan subassembly offer the facility of electrical contact for cable
shields. You can use the shield clamps provided
(see Reference Manual Module Specifications, Chapter 9).
To establish contact for the cable shields, strip the outer insulation in the region of
the shield clamp, and trap the cable shield under the shield clamp.
4.23

Routing Fiber-Optic Cables

Cable Routing
Indoor fiber-optic cables (for example, for connecting synchronization submodules)
are permitted for use in buildings, cable ducts, and channel trunking.
The maximum strain load when assembling is 1000 N and during operation 150 N.
Bending Radius
Minimum bending radius of the cables:
• At the connector: 55 mm
• Otherwise: 30 mm
4-38
Automation System S7-400 Hardware and Installation
A5E00850741-01