Siemens SIMATIC ET 200MP Equipment Manual page 56

Hide thumbs Also See for SIMATIC ET 200MP:
Table of Contents

Advertisement

ChannelError-
ExtendedChan-
Type
nel
ErrorType
0x0190
0x012C
0x0190
0x0193
Structure of the manufacturer-specific diagnostic data records (firmware version lower than
V4.2)
The structure of the diagnostic data records is differentiated by the BlockVersion. The
following BlockVersion applies to the IM 155-5 PN HF interface modules:
Table 6- 5
IM 155-5 MF HF interface module
6ES7155-5MU00-0CN0
Manufacturer-specific diagnostics in the User Structure Identifier (USI)
The following manufacturer-specific diagnostic data is signaled in the USI with the
IM 155-5 MF HF interface module:
Table 6- 6
Manufacturer-specific diagnostics in the USI
USI no. W#16#...
0001
0002
0003
0004
0005
0006
0007
Additional information
You can find additional information on maximum configuration, power budget and power
segments in the system manual S7-1500, ET 200MP Automation system
(https://support.industry.siemens.com/cs/ww/en/view/59191792).
Interface module IM 155-5 MF HF (6ES7155-5MU00-0CN0)
Equipment Manual, 11/2023, A5E53268530-AA
Associated value
(AddValue)
Signed
firmware update
Signed
firmware update
Structure of the manufacturer-specific diagnostic data records
Diagnostics
Power budget error (overload has been detected in at least one power segment)
Permitted number of power supply modules exceeded
Permitted number of I/O modules exceeded
No U connector detected on an IM port
More than one bus master module (IM/CPU) detected
Communication with slot <No.> has failed
Error IM power supply: Power supply not active or power supply active
Interrupts and diagnostic, error, and system alarms
Diagnostics
Security event: Firmware has been successfully downloaded
and activated for installation. (New firmware version: <FW
version>)
Security event: The firmware integrity checks failed. The new
firmware version <FW version> was rejected.
Verify if the firmware update file you are using comes from
a secure source.
Download the firmware again from the Siemens Support
Web page.
Repeat the firmware update.
BlockVersion
W#16#0101
6.3 Alarms
55

Advertisement

Table of Contents
loading